Brand Name : Ginri

Model Number : MDB-1Z

Certification : CE

Place of Origin : China

MOQ : 100Pcs

Payment Terms : L/C, T/T, Western Union,Paypal

Supply Ability : 50000Pcs per month

Delivery Time : 1-30 days upon order quantity

Packaging Details : Packed in cartons

Rated Voltage : 380VAC

Operating voltage range : +10/-15% max. of the rated voltage

Operating current range : 0.1-10A

Protection functions : Lock rotor

Indicators : LED indicating current,operation status

Output type : 1 C/O

Contact Now

0.1-10A Electronic Overload Relay Compressors motor protection relays

Description

Diemensions:70*67*98mm

Weight:300g

Protection Degree :IP 20

Output Type: 1 C/O

Contact Capacity: 5A 250VAC/30VDC

Indicators: LED indicating current

Protective Functions : Lock-rotor,Overcurrent,Undercurrent,Phase loss,Phase unbalance

Operating Current Range: 0.1-10A

Rated Supply Voltage : 220VAC,380VAC,50/60Hz

Operating Voltage Range:+10 / -15% Max Of The Rated Voltage

Features

1. Compact modular size with integrative structure

2. Built-in LED and keypad afford a precise,digital setting

3.Three-phase monitoring of short-circuit, locked-rotor,overcurrent,undervurrent, phase loss, phase unbalance

4. Adjustable reset mode:automatic reset or manual reset

5. Adjustable power-on delay

6. 1 C/O contact

Functions Data

Functions Condition & Setting Range Delay Time
Overcurrent

Condition : load current (in) exceeds

setting current (Is),i.e., In Is.
Setting range:as per model

Def:0.1~60s
Inv:1~5
Undercurrent Condition : load current (In) exceeds
setting current (uc),i.e.,In uc.
Setting range:0~80%*Is
0.1~60s
adjustable
Lock-rotor
(STALL
Condition : In Lock-rotor current setting (lr).
Active once motor starting.
Setting range:1.5*Is ~ 10*Is
0.1~60s
adjustable
Current
unbalance
(BL)

Condition : current unbalance setting unbalance(un)
Setting range:1%~50%

*Unbalance factor (%) = (Imax phase - Iaverage) / Iaverage) x 100%

0.1~60s
adjustable
Phase loss
(PL)
Condition : max unbalance is more than 50%
among 3 phase current.
Enable or disable : selectable
0.1~60s
adjustable

0.1-10A Electronic Overload Relay Compressors motor protection relays

GUARANTEE:

Guarantee for one year from shipped on board date. During the guarantee period, our company will provide the free easy-damaged spare part for problems caused by our quality of production or raw material, except the damageable spare parts caused by customer's incorrect man-made operation. After expiration, our company provides cost spare parts for maintenance.


Product Tags:

overload protection relay

      

current protection relay

      
 0.1-10A Electronic Overload Relay Compressors motor protection relays Manufactures

0.1-10A Electronic Overload Relay Compressors motor protection relays Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Wenzhou Ginri Power Automation Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)